7. Support Span
                    
     The distance between two consecutive supports is to be allowable. The allowable support span for horizontal pipe lines is given in Table-7


                                                                                                                       Table-7: Suggested Horizontal Pipe Support Spacing

Serial Number                               Nominal Pipe Size                                                  Suggested Maximum Span
                                                                       NPS        NPS                                        Water Service                     Steam, Gas, or Air Service
                                                                       Inch '      mm                                                  ' m                                                           'm
1                                                                          1             25                                                      2.1                                                           2.7
2                                                                         2             50                                                      3.0                                                         4.0
3                                                                         3             75                                                       3.7                                                          4.6
4                                                                        4             100                                                    4.3                                                           5.2
5                                                                         6             150                                                    5.2                                                           6.4
6                                                                         8             200                                                   5.8                                                           7.3
7                                                                         12             300                                                  7.0                                                           9.1
8                                                                         16            400                                                 8.2                                                            10.7
9                                                                         20            500                                                 9.1                                                             11.9
10                                                                       24            600                                                 9.8                                                             12.8

If the pipeline is inclined, the support span indicated in Table-7 can be based on the following assumptions:

                    Suggested maximum spacing between pipe supports for horizontal straight runs of standard and heavier pipe at maximum operating temperature of 750° F (400°C)
                    This table does not apply where span calculations are made or where there are concentrated loads between supports, such as flanges, valves, specialties, etc.,
                    The spacing is based on a fixed beam support with a bending stress no exceeding 2,300 psi (15.86 MPa) and insulated pipe filled with water or equivalent weight of steel pipe for                                                  steam, gas, or air services, and the pitch of the line is such that a sag of 0.1 Inch (2.5 mm) between supports is permissible.
                    